Heating and Cooling / Facade Heating & Cooling Products
Ventilation units for mixing ventilation LG-ZM-L-B and LG-ZUM-M-LB, for horizontal floor mounting
Decentralized air conditioning via the building facade.
To air condition office and administrative buildings having facades with floor-to-ceiling glazing, Krantz supplies ventilation units for raised floor mounting; they provide the required minimum percentage of outdoor air and remove the internal cooling and heating loads. The unit type LG-ZUM-M-LB has an additional function with recirculated air.
Features:
- Outdoor air intake directly through the facade; return air extraction via central system
- Cooling and heating via air-to-water heat exchanger
- Cooling with outdoor air (free cooling)
- Mixing & displacement ventilation close to facade
- Energy-efficient EC radial-flow fan
- F7 class filtration of outdoor air
Data:
Supply air volume flow rate:
33 l/s [120 m3/h]
Supply air temperature, summer:
18 °C (with outdoor air 32 °C / 40% relative humidity)
Total cooling output:
560 W
including:
-for cooling down 33 l/s [120 m3/h] of outdoor air:
240 W
-for cooling a room with tR = 26 °C:
320 W
Chilled water temperature:
15/17°C
Supply air temperature, winter:
34 °C (with outdoor air –12 °C)
Total heating output:
1 840 W
including:
– for heating up 33 l/s [120 m3/h] tR = 22 °C of outdoor air 1 360 W
– for room heating with tR = 22 °C: 480 W
Hot water temperature:
50 / 40 °C
Control signal for fan speed:
0 – 10 V DC
Effective power of fan:
20 W (volume flow = 120 m³/h)
Operating voltage:
30 V / 50 Hz
Downloads: